Instruction Manual
41
Configuring Powered Computers to Monitor a Managed UPS
Once you have added a Managed UPS, each server that is drawing
power through the UPS should be setup to monitor the UPS status as
a slave. This is done by installing the NUT package on each server, and
setting up upsmon to connect to the ECS0016.
Refer to the NUT documentation for details on how this is done,
specifically sections 13.5 to 13.10. http://eu1.networkupstools.org/
doc/2.2.0/INSTALL.html
An example upsmon.conf entry might look like:
MONITOR[email protected]1usernamepasswordslave
- managedups is the UPS Name of the Managed UPS
- 192.168.0.1 is the IP address of the ECS0016
- 1 indicates the server has a single power supply attached to this UPS